Produktdetails:
Zahlung und Versand AGB:
|
| Stromversorgung: | 12–30 V DC (Zweileiter) | Umgebungstemperatur: | -40 ° C bis 80 ° C (-40 ° F bis 176 ° F) |
|---|---|---|---|
| Elektrische Bewertung: | Universell einsetzbar, explosionsgeschützt, Eigensicherheit (abhängig von der Zertifizierung) | Zertifizierungen: | Zu den Standardmodellen gehören ATEX, IECEx, SIL 2 (konsultieren Sie das Handbuch für spezifische Be |
| Hervorheben: | MTL 4514D Fieldbus Power Supply,H1 Fieldbus Power Supply with Diagnostics,ATEX certified DIN Rail Power Supply |
||
MTL 4514D Fieldbus Power Supply | H1, 350mA, Diagnostics, IS, DIN Rail, ATEX/IECEx/FM Specs
MTL 4514D fieldbus power supply specifications. H1 fieldbus, 350 mA, advanced diagnostics, 24V DC, DIN rail. ATEX/IECEx/FM approved for hazardous areas.
The MTL 4514D is an advanced fieldbus power supply and conditioner from MTL's 4500 series, designed to provide regulated power, signal conditioning, and diagnostic monitoring for FOUNDATION Fieldbus H1 and PROFIBUS PA networks. This device delivers 350 mA of fieldbus power, features advanced diagnostic capabilities (indicated by the "D" suffix), provides short-circuit and overload protection, and carries ATEX, IECEx, and FM approvals for hazardous area installations. The 4514D offers enhanced monitoring for critical fieldbus segments.
|
Parameter |
Specification |
|---|---|
|
Model Number |
4514D |
|
Product Series |
MTL 4500 Series |
|
Product Type |
Advanced Fieldbus Power Conditioner with Diagnostics and Intrinsic Safety |
|
Safety Standard |
Intrinsic Safety (IS) |
|
Approvals |
ATEX, IECEx, FM (see specific certifications) |
|
Hazardous Area Rating |
Zone 1, IIC, T6 (Gas), A21, T85°C (Dust) |
|
Network Type |
FOUNDATION Fieldbus H1, PROFIBUS PA |
|
Power Specifications |
|
|
Input Voltage |
20-30V DC (typically 24V DC) |
|
Input Current |
600 mA maximum |
|
Input Power |
15W maximum |
|
Output Voltage |
20-24V DC (regulated) |
|
Output Current |
350 mA (maximum continuous) |
|
Current Limiting |
Electronic, adjustable via DIP switches |
|
Short Circuit Protection |
Yes, with auto-recovery |
|
Overload Protection |
Yes, with auto-recovery |
|
Diagnostic Features |
|
|
Segment Monitoring |
Voltage, current, device count (estimated) |
|
Status Indication |
Multi-color LED with status patterns |
|
Communication Interface |
RS-485 (Modbus RTU) for remote diagnostics |
|
Event Logging |
Configurable alarms and events |
|
Communications Specifications |
|
|
Signal Conditioning |
Built-in, ensures communication integrity |
|
Termination |
Built-in 100 Ω termination (switchable) |
|
Baud Rate |
31.25 kbps (Fieldbus H1, PROFIBUS PA) |
|
General Specifications |
|
|
Operating Temperature |
-20°C to +60°C (-4°F to +140°F) |
|
Storage Temperature |
-40°C to +85°C (-40°F to 185°F) |
|
Relative Humidity |
0-95% non-condensing |
|
Connection Type |
Screw terminals |
|
Wire Size |
0.2-2.5 mm² (24-12 AWG) |
|
Mounting |
DIN rail 35mm |
|
Degree of Protection |
IP20 (requires enclosure) |
|
Dimensions (W × H × D) |
22.5 × 124 × 115 mm |
|
Weight |
Approx. 320 g |
|
Housing Material |
Polycarbonate/PBT |
|
LED Indicators |
Multi-color status LED (Green/Yellow/Red) |
|
Configuration |
DIP switches for current limit and termination |
|
Certifications |
ATEX, IECEx, FM, CSA, DNV GL, Marine, SIL 2 capable |
Note: Specifications are based on MTL 4500 series documentation. The "D" suffix indicates diagnostic capabilities. Always verify with the latest product datasheet.
Advanced Diagnostics: Real-time monitoring of segment voltage, current, and estimated device count
Adjustable Current Limit: Configurable via DIP switches (typically 100-350 mA)
RS-485 Communication: Remote diagnostic access via Modbus RTU protocol
Intrinsic Safety: Approved for Zone 1 hazardous locations
Built-in Termination: Switchable 100 Ω termination resistor
Multi-color Status LED: Visual indication of operating state and faults
Event Logging: Stores diagnostic events for troubleshooting
Compact Design: DIN rail mounting for easy panel installation
Global Approvals: Certified for international hazardous area applications
SIL 2 Capable: Suitable for safety instrumented systems when properly configured
|
Parameter |
Minimum |
Typical |
Maximum |
Unit |
|---|---|---|---|---|
|
Input Voltage |
20 |
24 |
30 |
V DC |
|
Output Voltage |
20 |
22 |
24 |
V DC |
|
Output Current |
0 |
- |
350 |
mA |
|
Current Limit Settings |
100, 150, 200, 250, 300, 350 |
- |
- |
mA |
|
Ripple and Noise |
- |
50 |
100 |
mV p-p |
|
Load Regulation |
- |
±0.5% |
±1% |
of Vout |
|
Response Time |
- |
< 50 |
100 |
µs |
|
Efficiency |
- |
88% |
- |
- |
|
LED Color |
Pattern |
Meaning |
|---|---|---|
|
Green |
Solid |
Normal operation |
|
Green |
Flashing (1 Hz) |
Communications activity |
|
Yellow |
Solid |
Warning condition (e.g., approaching current limit) |
|
Yellow |
Flashing (1 Hz) |
Configuration mode |
|
Red |
Solid |
Fault condition (short circuit, overload) |
|
Red |
Flashing (4 Hz) |
Over-temperature warning |
|
Off |
- |
No power or internal failure |
|
Parameter |
Access Method |
Description |
|---|---|---|
|
Segment Voltage |
Modbus Register |
Real-time segment voltage measurement |
|
Segment Current |
Modbus Register |
Real-time segment current consumption |
|
Estimated Device Count |
Modbus Register |
Calculated from current draw |
|
Status Flags |
Modbus Register |
Fault, warning, communication status |
|
Temperature |
Modbus Register |
Internal temperature measurement |
|
Event Log |
Modbus Registers |
Stored diagnostic events |
|
Parameter |
Symbol |
Value |
Unit |
|---|---|---|---|
|
Maximum Output Voltage (Uo) |
Uo |
24 |
V |
|
Maximum Output Current (Io) |
Io |
350 |
mA |
|
Maximum Output Power (Po) |
Po |
8.4 |
W |
|
Maximum External Capacitance (Co) |
Co |
According to connected apparatus |
nF |
|
Maximum External Inductance (Lo) |
Lo |
According to connected apparatus |
mH |
Note: The 4514D is an associated apparatus. All connected fieldbus devices must be intrinsically safe certified.
|
Switch |
Function |
Position 1 |
Position 0 |
|---|---|---|---|
|
1 |
Current Limit Bit 0 |
- |
- |
|
2 |
Current Limit Bit 1 |
- |
- |
|
3 |
Current Limit Bit 2 |
- |
- |
|
4 |
Termination |
ON |
OFF |
|
5 |
Reserved |
- |
- |
|
6 |
Reserved |
- |
- |
Note: Specific DIP switch settings for current limit vary by model. Consult installation manual.
Critical Process Control: Fieldbus segments requiring diagnostic monitoring
Safety Instrumented Systems: SIL 2 applications with diagnostic requirements
Remote Monitoring: Applications where segment health monitoring is valuable
Predictive Maintenance: Facilities using diagnostic data for maintenance planning
Large Fieldbus Networks: Multiple segments where proactive monitoring prevents downtime
Offshore/Remote Installations: Where quick fault diagnosis is critical
Pharmaceutical/BioTech: Regulated industries requiring diagnostic evidence
Power Generation: Critical measurement and control networks
Power Supply Requirements: Requires a 20-30V DC input with sufficient capacity. Recommended: 24V DC, 1A minimum.
Current Limit Setting: Configure via DIP switches based on connected device load. Allow 10-20% margin above calculated load.
Termination Setting: Set DIP switch 4 to ON if this unit is at segment end. Each segment needs termination at both ends only.
Diagnostic Access: RS-485 interface allows remote monitoring. Requires proper network setup (address, baud rate, parity).
LED Diagnostics: Multi-color LED provides immediate status. Solid red indicates fault requiring investigation.
Certification Compliance: Verify certifications match hazardous area classification (Zone 1, IIC, T6).
Thermal Management: Ensure adequate ventilation, especially at high ambient temperatures or near current limit.
Grounding: Follow manufacturer's grounding instructions for noise immunity and safety.
SIL Applications: For SIL 2 use, follow all manufacturer guidelines for configuration, installation, and proof testing.
Event Log: Review event log periodically for early detection of developing issues (e.g., increasing current trends).
Note: This data sheet provides general specifications for the MTL 4514D advanced fieldbus power supply. For complete installation guidelines, DIP switch settings, Modbus register map, diagnostic configuration, and safety instructions, consult the official MTL 4500 Series Technical Manual and 4514D Diagnostic Guide. Always verify that the product configuration and certifications match your specific application requirements.
Founded in 2012, ACH is a top-tier distributor of industrial automation products, supplying genuine devices from leading brands like ABB, P+F, E&H, AB, MTL and EMERSON to emerging markets worldwide. Our mission is to provide 100% Genuine products at the most competitive prices, helping customers reduce costs and strengthen their market position.
Long-term brand partners can get competitive product prices. At the same time, ACH controls the profit per order to 5%, providing the most competitive prices.
Yes, all products from ACH are certified genuine OEM units. We acquire our inventory through official OEM channels and trusted third-party suppliers, ensuring every item is authentic and reliable.
We'll handle the shipping for you. Through our partnerships, we can secure competitive rates with major carriers like FedEx, DHL, TNT, and UPS, ensuring a smooth and cost-effective delivery.
One-year Warranty.
Products are divided into spot and futures, and the delivery period of different brands of products is also different. For details, please contact the ACH business manager.
Ansprechpartner: sales2