商品の詳細:
お支払配送条件:
|
| 電源: | DC12~30V(2線式) | 周囲温度: | -40°C〜80°C(-40°F〜176°F) |
|---|---|---|---|
| 電気定格: | 汎用、防爆、本質安全防爆(認定に応じて) | 認証: | 標準モデルには、ATEX、IECEx、SIL 2 が含まれます (特定の定格についてはマニュアルを参照してください) |
| ハイライト: | MTL 4632 Fieldbus Power Module,DIN Rail Fieldbus Power Module,ATEX IECEx Safety Barrier Module |
||
MTL 4632 Fieldbus Power Module | H1, IS, 350mA, DIN Rail, ATEX/IECEx, Diagnostics Specs
Meta Description: MTL 4632 fieldbus power and communications module specifications. Fieldbus H1, 350 mA, intrinsic safety, DIN rail, diagnostic features. ATEX/IECEx approved for hazardous areas.
The MTL 4632 is a fieldbus power and communications module from MTL's 4600 series, designed to provide regulated power and signal conditioning for FOUNDATION Fieldbus H1 and PROFIBUS PA networks in hazardous areas. This device delivers 350 mA of fieldbus power, includes advanced diagnostic capabilities, provides intrinsic safety protection, and carries ATEX and IECEx approvals for Zone 1 hazardous locations. The 4632 ensures reliable network operation with enhanced monitoring features for modern fieldbus installations.
|
Parameter |
Specification |
|---|---|
|
Model Number |
4632 |
|
Product Series |
MTL 4600 Series |
|
Product Type |
Fieldbus Power and Communications Module with Diagnostics and Intrinsic Safety |
|
Safety Standard |
Intrinsic Safety (IS) |
|
Approvals |
ATEX, IECEx (see specific certifications) |
|
Hazardous Area Rating |
Zone 1, IIC, T6 (Gas), A21, T85°C (Dust) |
|
Network Type |
FOUNDATION Fieldbus H1, PROFIBUS PA |
|
Power Specifications |
|
|
Input Voltage |
20-30V DC (typically 24V DC) |
|
Input Current |
600 mA maximum |
|
Input Power |
15W maximum |
|
Output Voltage |
20-24V DC (regulated) |
|
Output Current |
350 mA (maximum continuous) |
|
Current Limit |
Adjustable via configuration |
|
Short Circuit Protection |
Electronic, fast-acting with auto-recovery |
|
Communications Specifications |
|
|
Baud Rate |
31.25 kbps (Fieldbus H1, PROFIBUS PA) |
|
Termination |
Built-in 100 Ω termination (software configurable) |
|
Isolation |
500V AC (field to system) |
|
Diagnostic Features |
|
|
Real-time Monitoring |
Voltage, current, power, device count |
|
Fault Detection |
Short circuit, overload, communication faults |
|
Status Indicators |
Multi-color LEDs with status patterns |
|
Communication Interface |
RS-485 for configuration and diagnostics (optional) |
|
Event Logging |
Configurable alarm and event recording |
|
General Specifications |
|
|
Operating Temperature |
-20°C to +60°C (-4°F to +140°F) |
|
Storage Temperature |
-40°C to +85°C (-40°F to 185°F) |
|
Relative Humidity |
0-95% non-condensing |
|
Connection Type |
Screw terminals |
|
Wire Size |
0.2-2.5 mm² (24-12 AWG) |
|
Mounting |
DIN rail 35mm |
|
Degree of Protection |
IP20 (requires enclosure) |
|
Dimensions (W × H × D) |
22.5 × 124 × 115 mm |
|
Weight |
Approx. 320 g |
|
Housing Material |
Polycarbonate/PBT |
|
LED Indicators |
Power, Communication, Segment Status, Fault |
|
Configuration |
Software configurable (via optional interface) |
|
Certifications |
ATEX, IECEx, FM, CSA, DNV GL, Marine, SIL 2 capable |
Note: Specifications are based on MTL 4600 series documentation. The 4632 includes enhanced diagnostics and configuration options compared to earlier models. Always verify with the latest product datasheet.
Advanced Diagnostics: Real-time monitoring of voltage, current, and power consumption
350 mA Power Capacity: Suitable for medium-density fieldbus networks
Software Configuration: Flexible setup via configuration software
Intrinsic Safety: Approved for Zone 1 hazardous locations
Adjustable Current Limit: Field-configurable for different segment requirements
Built-in Termination: Configurable 100 Ω termination
Event Logging: Records alarms and events for troubleshooting
Multi-color LEDs: Detailed status indication through LED patterns
Compact Design: DIN rail mounting for easy panel integration
Global Approvals: Certified for international hazardous area applications
SIL 2 Capable: Suitable for safety applications when properly configured
|
Parameter |
Minimum |
Typical |
Maximum |
Unit |
|---|---|---|---|---|
|
Input Voltage |
20 |
24 |
30 |
V DC |
|
Output Voltage |
20 |
22 |
24 |
V DC |
|
Output Current |
0 |
- |
350 |
mA |
|
Ripple and Noise |
- |
50 |
100 |
mV p-p |
|
Load Regulation |
- |
±0.5% |
±1% |
of Vout |
|
Response Time |
- |
< 50 |
100 |
µs |
|
Efficiency |
- |
88% |
- |
- |
|
LED |
Color |
Pattern |
Meaning |
|---|---|---|---|
|
PWR |
Green |
Solid |
Input power present |
|
PWR |
Green |
Flashing |
Configuration mode |
|
COM |
Green |
Solid |
Communications active |
|
COM |
Green |
Flashing (1Hz) |
Communications activity |
|
COM |
Yellow |
Flashing (4Hz) |
Configuration in progress |
|
SEG |
Green |
Solid |
Segment operating normally |
|
SEG |
Red |
Solid |
Segment fault (short, overload) |
|
SEG |
Red |
Flashing |
Warning condition (approaching limits) |
|
FAULT |
Red |
Solid |
Module fault |
|
FAULT |
Red |
Flashing |
Recoverable fault condition |
|
Parameter |
Symbol |
Value |
Unit |
|---|---|---|---|
|
Maximum Output Voltage (Uo) |
Uo |
24 |
V |
|
Maximum Output Current (Io) |
Io |
350 |
mA |
|
Maximum Output Power (Po) |
Po |
8.4 |
W |
|
Maximum External Capacitance (Co) |
Co |
According to connected apparatus |
nF |
|
Maximum External Inductance (Lo) |
Lo |
According to connected apparatus |
mH |
Note: The 4632 is an associated apparatus. All connected fieldbus devices in the hazardous area must be certified as intrinsically safe.
|
Parameter |
Monitoring Capability |
Alarm Thresholds |
|---|---|---|
|
Output Voltage |
Real-time measurement |
Configurable high/low |
|
Output Current |
Real-time measurement |
Configurable overload |
|
Power Consumption |
Calculated real-time |
Configurable limit |
|
Device Count |
Estimated from current |
- |
|
Temperature |
Internal monitoring |
Over-temperature warning |
|
Communication Health |
Signal quality |
Error rate monitoring |
[Control System]
|
[Fieldbus Master/Card]
|
[MTL 4632 Power Module]
|
[Fieldbus Segment]
|
[Field Devices: Transmitters, Valves, etc.]
Medium-Density Fieldbus Networks: Process areas with multiple but not extreme device counts
Safety Instrumented Systems: SIL 2 applications requiring diagnostic monitoring
Remote Monitoring Applications: Where detailed segment health information is valuable
Predictive Maintenance Programs: Facilities using diagnostic data for maintenance planning
Process Optimization: Applications requiring detailed power and device monitoring
Tank Farms and Pipelines: Distributed measurement and control networks
Power Generation: Fieldbus networks in turbine and boiler control
Water Treatment: Monitoring and control networks with diagnostic requirements
Power Supply Requirements: Requires a 24V DC power supply capable of providing at least 600 mA. Consider inrush current and derating for high temperatures.
Configuration Requirements: The 4632 offers enhanced configuration options via software. Initial setup requires configuration for current limits, alarm thresholds, and termination settings.
Current Limit Setting: The adjustable current limit allows optimization for specific segment requirements. Set appropriately for the connected devices plus margin.
Diagnostic Utilization: Leverage the diagnostic capabilities for preventive maintenance. Monitor trends in current consumption and voltage for early detection of issues.
RS-485 Interface: The optional RS-485 interface enables remote configuration and diagnostics. Ensure proper network design if implemented.
Termination Management: The configurable termination allows flexible network design. Remember that each segment requires termination at both ends.
Certification Compliance: Verify that the 4632's specific certifications match the hazardous area classification (Zone 1, IIC, T6) of your installation.
Thermal Management: Ensure adequate ventilation, especially when operating near maximum capacity. The module includes temperature monitoring for self-protection.
Event Logging: The event log can be valuable for troubleshooting intermittent issues. Configure appropriate event recording based on application needs.
SIL Applications: For SIL 2 applications, follow all manufacturer guidelines for configuration, installation, and proof testing to maintain safety integrity.
Note: This data sheet provides general specifications for the MTL 4632 fieldbus power and communications module. For complete installation guidelines, configuration procedures, diagnostic implementation, and safety instructions, consult the official MTL 4600 Series Technical Manual and 4632 Configuration Guide. Always verify that the product configuration and certifications match your specific application requirements.
![]()
Founded in 2012, ACH is a top-tier distributor of industrial automation products, supplying genuine devices from leading brands like ABB, P+F, E&H, AB, MTL and EMERSON to emerging markets worldwide. Our mission is to provide 100% Genuine products at the most competitive prices, helping customers reduce costs and strengthen their market position.
Long-term brand partners can get competitive product prices. At the same time, ACH controls the profit per order to 5%, providing the most competitive prices.
Yes, all products from ACH are certified genuine OEM units. We acquire our inventory through official OEM channels and trusted third-party suppliers, ensuring every item is authentic and reliable.
We'll handle the shipping for you. Through our partnerships, we can secure competitive rates with major carriers like FedEx, DHL, TNT, and UPS, ensuring a smooth and cost-effective delivery.
One-year Warranty.
Products are divided into spot and futures, and the delivery period of different brands of products is also different. For details, please contact the ACH business manager.
コンタクトパーソン: sales2