Détails sur le produit:
Conditions de paiement et expédition:
|
| Alimentation: | 12-30 V CC (deux fils) | Température ambiante: | -40 ° C à 80 ° C (-40 ° F à 176 ° F) |
|---|---|---|---|
| Évaluation électrique: | Usage général, antidéflagrant, sécurité intrinsèque (dépend de la certification) | Certifications: | Les modèles standard incluent ATEX, IECEx, SIL 2 (consulter le manuel pour les valeurs spécifiques) |
| Mettre en évidence: | MTL 4521 dual channel fieldbus supply,DIN rail safety barrier with warranty,ATEX IECEx FM certified fieldbus supply |
||
MTL 4521 Dual Channel Fieldbus Supply | 2x 350mA, IS, DIN Rail, ATEX/IECEx/FM Specs
MTL 4521 dual-channel fieldbus power supply specifications. Two independent H1/PA segments, 350mA each, 24V DC, DIN rail. ATEX/IECEx/FM approved for hazardous areas.
The MTL 4521 is a dual-channel fieldbus power supply and conditioner from MTL's 4500 series, designed to provide regulated power and signal conditioning for two independent FOUNDATION Fieldbus H1 or PROFIBUS PA segments. Each channel delivers 350 mA of fieldbus power, provides short-circuit protection, includes independently switchable termination, and carries ATEX, IECEx, and FM approvals for Zone 1 hazardous area installations. The 4521 provides a space-efficient solution for powering two separate fieldbus networks from a single unit.
|
Parameter |
Specification |
|---|---|
|
Model Number |
4521 |
|
Product Series |
MTL 4500 Series |
|
Product Type |
Dual-Channel Fieldbus Power Conditioner with Intrinsic Safety |
|
Safety Standard |
Intrinsic Safety (IS) |
|
Approvals |
ATEX, IECEx, FM (see specific certifications) |
|
Hazardous Area Rating |
Zone 1, IIC, T6 (Gas), A21, T85°C (Dust) |
|
Network Type |
FOUNDATION Fieldbus H1, PROFIBUS PA |
|
Power Specifications |
|
|
Input Voltage |
20-30V DC (typically 24V DC) |
|
Input Current |
1.2A maximum (both channels) |
|
Input Power |
30W maximum |
|
Output Voltage (per channel) |
20-24V DC (regulated) |
|
Output Current (per channel) |
350 mA (maximum continuous, per channel) |
|
Total Output Current |
500 mA (maximum combined, limited by input) |
|
Current Limiting |
Electronic, per channel |
|
Short Circuit Protection |
Yes, per channel, with auto-recovery |
|
Communications Specifications |
|
|
Signal Conditioning |
Built-in, per channel |
|
Termination |
Built-in 100 Ω termination per channel (independently switchable) |
|
Baud Rate |
31.25 kbps (Fieldbus H1, PROFIBUS PA) |
|
Channel Isolation |
Channels are isolated from each other |
|
General Specifications |
|
|
Operating Temperature |
-20°C to +60°C (-4°F to +140°F) |
|
Storage Temperature |
-40°C to +85°C (-40°F to 185°F) |
|
Relative Humidity |
0-95% non-condensing |
|
Connection Type |
Screw terminals |
|
Wire Size |
0.2-2.5 mm² (24-12 AWG) |
|
Mounting |
DIN rail 35mm |
|
Degree of Protection |
IP20 (requires enclosure) |
|
Dimensions (W × H × D) |
45.0 × 124 × 115 mm |
|
Weight |
Approx. 600 g |
|
Housing Material |
Polycarbonate/PBT |
|
LED Indicators |
Per channel: Power (Green), Communication (Green), Fault (Red) |
|
Termination Switches |
Yes, two independent switches |
|
Certifications |
ATEX, IECEx, FM, CSA, DNV GL, Marine |
Note: Specifications are based on MTL 4500 series documentation. The 4521 provides two completely independent 350mA channels in a compact housing. Always verify with the latest product datasheet.
Dual Independent Channels: Two completely isolated 350mA fieldbus segments in one unit
Space Efficiency: Saves panel space compared to two single-channel units
Independent Termination Control: Separate switches for each channel's 100Ω termination
Independent Fault Protection: Short-circuit and overload protection per channel
Intrinsic Safety: Approved for Zone 1 hazardous locations
LED Status per Channel: Individual power, communication, and fault indicators for each segment
Global Approvals: Certified for international hazardous area applications
No Configuration Required: Plug-and-play operation
Channel Isolation: Prevents cross-talk and fault propagation between segments
Cost-Effective: Lower cost per channel than single units
|
Parameter |
Minimum |
Typical |
Maximum |
Unit |
|---|---|---|---|---|
|
Input Voltage |
20 |
24 |
30 |
V DC |
|
Output Voltage |
20 |
22 |
24 |
V DC |
|
Output Current (per channel) |
0 |
- |
350 |
mA |
|
Combined Output Current |
- |
- |
500 |
mA |
|
Ripple and Noise |
- |
50 |
100 |
mV p-p |
|
Load Regulation |
- |
±0.5% |
±1% |
of Vout |
|
Response Time |
- |
< 100 |
200 |
µs |
|
Channel-to-Channel Isolation |
500 |
- |
- |
V AC |
|
LED |
Color |
State |
Meaning |
|---|---|---|---|
|
PWR (Power) |
Green |
Solid On |
Input power present, channel enabled |
|
PWR (Power) |
Off |
- |
No input power or internal fault |
|
COM (Communication) |
Green |
Solid On |
Communications active on this segment |
|
COM (Communication) |
Flashing Green |
- |
Communications activity detected |
|
COM (Communication) |
Off |
- |
No communications activity |
|
FAULT |
Red |
Solid On |
Output fault (short circuit, overload, over-temperature) on this channel |
|
FAULT |
Off |
- |
Normal operation |
|
Parameter |
Symbol |
Value |
Unit |
|---|---|---|---|
|
Maximum Output Voltage (Uo) |
Uo |
24 |
V |
|
Maximum Output Current (Io) |
Io |
350 |
mA |
|
Maximum Output Power (Po) |
Po |
8.4 |
W |
|
Maximum External Capacitance (Co) |
Co |
According to connected apparatus |
nF |
|
Maximum External Inductance (Lo) |
Lo |
According to connected apparatus |
mH |
Note: The 4521 is an associated apparatus. Each channel's connected fieldbus devices must be intrinsically safe certified.
Multi-Segment Control Systems: Powering two separate fieldbus segments from one location
Redundant Systems: Independent power for redundant fieldbus networks
Process Units with Multiple Loops: Separating control loops for different process areas
Backup Power Distribution: Primary and backup segments in critical applications
Panel Space Optimization: Where rack space is limited
Cost-Sensitive Multi-Segment Installations: Reducing per-channel cost
Batch Process Sequencing: Independent control of different batch stages
Safety and Control Separation: Separate segments for safety and basic process control systems
Power Supply Requirements: Requires a robust 20-30V DC input. Recommended: 24V DC, 2A capacity to support both channels at full load (500mA combined maximum).
Current Sharing: The 500mA combined maximum means both channels cannot run at full 350mA simultaneously. Maximum combined load is 500mA (e.g., 250mA per channel).
Independent Operation: Channels are electrically isolated. A fault on one channel does not affect the other.
Termination Settings: Each channel's termination must be set independently based on segment topology. Typically, only one terminator per segment end.
Wiring Separation: Maintain separation between fieldbus cables of different segments, especially in cable trays.
Thermal Considerations: The 4521 may generate significant heat with both channels near maximum. Ensure adequate ventilation and derate at high ambient temperatures.
Grounding: Follow manufacturer's grounding instructions. Fieldbus shields should typically be grounded at the power supply end only.
Certification Compliance: Verify certifications match hazardous area classification. Each channel has its own entity parameters for IS calculations.
LED Diagnostics: Individual channel LEDs simplify troubleshooting. Red FAULT on one channel only affects that segment.
Segment Design: Design each segment independently according to fieldbus rules (max 32 devices, 1900m trunk, etc.).
Note: This data sheet provides general specifications for the MTL 4521 dual-channel fieldbus power supply. For complete installation guidelines, wiring diagrams, network design rules, and safety instructions, consult the official MTL 4500 Series Technical Manual. Always verify that the product configuration and certifications match your specific application requirements.
![]()
Founded in 2012, ACH is a top-tier distributor of industrial automation products, supplying genuine devices from leading brands like ABB, P+F, E&H, AB, MTL and EMERSON to emerging markets worldwide. Our mission is to provide 100% Genuine products at the most competitive prices, helping customers reduce costs and strengthen their market position.
Long-term brand partners can get competitive product prices. At the same time, ACH controls the profit per order to 5%, providing the most competitive prices.
Yes, all products from ACH are certified genuine OEM units. We acquire our inventory through official OEM channels and trusted third-party suppliers, ensuring every item is authentic and reliable.
We'll handle the shipping for you. Through our partnerships, we can secure competitive rates with major carriers like FedEx, DHL, TNT, and UPS, ensuring a smooth and cost-effective delivery.
One-year Warranty.
Products are divided into spot and futures, and the delivery period of different brands of products is also different. For details, please contact the ACH business manager.
Personne à contacter: sales2