Detalhes do produto:
Condições de Pagamento e Envio:
|
| Fonte de energia: | 12-30 V CC (dois fios) | Temperatura ambiente: | -40 ° C a 80 ° C (-40 ° F a 176 ° F) |
|---|---|---|---|
| Classificação Elétrica: | Uso geral, à prova de explosão, segurança intrínseca (depende da certificação) | Certificações: | Os modelos padrão incluem ATEX, IECEx, SIL 2 (consulte o manual para classificações específicas) |
| Destacar: | MTL 4541 Fieldbus Power Module,Fieldbus Power Module with Diagnostics,DIN Rail Power Module ATEX certified |
||
MTL 4541 Fieldbus Power Module | H1, 350mA, Diagnostics, IS, DIN Rail, ATEX/IECEx/FM Specs
MTL 4541 fieldbus power and communications module specifications. H1/PA network, 350 mA, advanced diagnostics, 24V DC, DIN rail. ATEX/IECEx/FM approved for hazardous areas.
The MTL 4541 is an advanced fieldbus power and communications module from MTL's 4500 series, designed to provide regulated power, signal conditioning, and diagnostic capabilities for FOUNDATION Fieldbus H1 and PROFIBUS PA networks. This device delivers 350 mA of fieldbus power, features integrated diagnostics, provides short-circuit and overload protection, and carries ATEX, IECEx, and FM approvals for Zone 1 hazardous area installations. The 4541 represents a comprehensive solution for fieldbus networks requiring both reliable power and system monitoring.
|
Parameter |
Specification |
|---|---|
|
Model Number |
4541 |
|
Product Series |
MTL 4500 Series |
|
Product Type |
Advanced Fieldbus Power and Communications Module with Intrinsic Safety |
|
Safety Standard |
Intrinsic Safety (IS) |
|
Approvals |
ATEX, IECEx, FM (see specific certifications) |
|
Hazardous Area Rating |
Zone 1, IIC, T6 (Gas), A21, T85°C (Dust) |
|
Network Type |
FOUNDATION Fieldbus H1, PROFIBUS PA |
|
Power Specifications |
|
|
Input Voltage |
20-30V DC (typically 24V DC) |
|
Input Current |
600 mA maximum |
|
Input Power |
15W maximum |
|
Output Voltage |
20-24V DC (regulated) |
|
Output Current |
350 mA (maximum continuous) |
|
Current Limiting |
Electronic, adjustable |
|
Short Circuit Protection |
Yes, with auto-recovery and diagnostic reporting |
|
Overload Protection |
Yes, with diagnostic reporting |
|
Diagnostic Features |
|
|
Segment Monitoring |
Voltage, current, device count (estimated) |
|
Status Indication |
Multi-color LED with diagnostic patterns |
|
Communication Interface |
Optional RS-485 for configuration/diagnostics |
|
Fault Logging |
Configurable event recording |
|
Communications Specifications |
|
|
Signal Conditioning |
Built-in, ensures communication integrity |
|
Termination |
Built-in 100 Ω termination (switchable) |
|
Baud Rate |
31.25 kbps (Fieldbus H1, PROFIBUS PA) |
|
General Specifications |
|
|
Operating Temperature |
-20°C to +60°C (-4°F to +140°F) |
|
Storage Temperature |
-40°C to +85°C (-40°F to 185°F) |
|
Relative Humidity |
0-95% non-condensing |
|
Connection Type |
Screw terminals |
|
Wire Size |
0.2-2.5 mm² (24-12 AWG) |
|
Mounting |
DIN rail 35mm |
|
Degree of Protection |
IP20 (requires enclosure) |
|
Dimensions (W × H × D) |
22.5 × 124 × 115 mm |
|
Weight |
Approx. 320 g |
|
Housing Material |
Polycarbonate/PBT |
|
LED Indicators |
Multi-color status LED (Green/Yellow/Red) with diagnostic patterns |
|
Configuration |
DIP switches for basic settings |
|
Certifications |
ATEX, IECEx, FM, CSA, DNV GL, Marine, SIL 2 capable |
Note: Specifications are based on MTL 4500 series documentation. The 4541 includes enhanced diagnostics and monitoring capabilities. Always verify with the latest product datasheet.
Advanced Diagnostics: Real-time monitoring of segment voltage, current, and estimated device count
Adjustable Current Limit: Configurable via internal DIP switches
Multi-color Status LED: Visual indication of operating state, warnings, and faults
Optional Communication Interface: RS-485 for remote monitoring and configuration
Intrinsic Safety: Approved for Zone 1 hazardous locations
Built-in Termination: Switchable 100 Ω termination resistor
Fault Logging: Records diagnostic events for troubleshooting
Compact Design: DIN rail mounting for easy panel installation
Global Approvals: Certified for international hazardous area applications
SIL 2 Capable: Suitable for safety instrumented systems when properly configured
|
Parameter |
Minimum |
Typical |
Maximum |
Unit |
|---|---|---|---|---|
|
Input Voltage |
20 |
24 |
30 |
V DC |
|
Output Voltage |
20 |
22 |
24 |
V DC |
|
Output Current |
0 |
- |
350 |
mA |
|
Current Limit Settings |
100, 150, 200, 250, 300, 350 |
- |
- |
mA |
|
Ripple and Noise |
- |
50 |
100 |
mV p-p |
|
Load Regulation |
- |
±0.5% |
±1% |
of Vout |
|
Response Time |
- |
< 50 |
100 |
µs |
|
Efficiency |
- |
88% |
- |
- |
|
LED Color |
Pattern |
Meaning |
|---|---|---|
|
Green |
Solid |
Normal operation, segment healthy |
|
Green |
Flashing (1 Hz) |
Communications activity detected |
|
Yellow |
Solid |
Warning condition (e.g., approaching current limit) |
|
Yellow |
Flashing (1 Hz) |
Configuration mode active |
|
Red |
Solid |
Fault condition (short circuit, overload, over-temperature) |
|
Red |
Flashing (2 Hz) |
Communication fault |
|
Red |
Flashing (4 Hz) |
Over-temperature warning |
|
Off |
- |
No power or internal failure |
|
Parameter |
Monitoring Method |
Diagnostic Value |
|---|---|---|
|
Segment Voltage |
Real-time measurement |
Early detection of wiring issues |
|
Segment Current |
Real-time measurement |
Load monitoring and overload prediction |
|
Estimated Device Count |
Calculated from current |
Device presence monitoring |
|
Internal Temperature |
Sensor measurement |
Thermal management |
|
Communication Health |
Signal quality monitoring |
Network integrity assessment |
|
Parameter |
Symbol |
Value |
Unit |
|---|---|---|---|
|
Maximum Output Voltage (Uo) |
Uo |
24 |
V |
|
Maximum Output Current (Io) |
Io |
350 |
mA |
|
Maximum Output Power (Po) |
Po |
8.4 |
W |
|
Maximum External Capacitance (Co) |
Co |
According to connected apparatus |
nF |
|
Maximum External Inductance (Lo) |
Lo |
According to connected apparatus |
mH |
Note: The 4541 is an associated apparatus. All connected fieldbus devices must be intrinsically safe certified.
|
Switch |
Function |
Position 1 |
Position 0 |
|---|---|---|---|
|
1-3 |
Current Limit |
Binary coded setting |
(See manual for codes) |
|
4 |
Termination |
ON |
OFF |
|
5 |
Reserved/Diagnostic Mode |
- |
- |
|
6 |
Reserved/Communication |
- |
- |
Note: DIP switch configurations vary by model and firmware. Consult the installation manual for specific settings.
Critical Process Control: Fieldbus segments requiring continuous health monitoring
Safety Instrumented Systems: SIL 2 applications with diagnostic requirements
Predictive Maintenance Programs: Facilities using diagnostic data for maintenance scheduling
Remote Monitoring Installations: Where segment health information is valuable off-site
Large Fieldbus Networks: Proactive monitoring to prevent unplanned downtime
Regulated Industries: Pharmaceutical, food & beverage requiring diagnostic evidence
Offshore/Remote Platforms: Where quick fault diagnosis reduces maintenance costs
Power Generation: Critical measurement and control networks
Power Supply Requirements: Requires a 20-30V DC input with sufficient capacity. Recommended: 24V DC, 1A minimum.
Current Limit Setting: Configure via DIP switches based on connected device load. Include 10-20% safety margin.
Diagnostic Utilization: Leverage the diagnostic LED patterns for immediate troubleshooting. Yellow indicates conditions that may become faults.
Termination Setting: Set DIP switch 4 appropriately. Each segment requires termination at both ends only.
RS-485 Interface: Optional interface enables remote monitoring. Requires proper network setup if implemented.
Certification Compliance: Verify certifications match hazardous area classification (Zone 1, IIC, T6).
Thermal Management: Ensure adequate ventilation, especially at high ambient temperatures or near current limit.
Grounding: Follow manufacturer's grounding instructions for optimal noise immunity and safety.
SIL Applications: For SIL 2 use, follow all manufacturer guidelines for configuration, proof testing, and maintenance.
Preventive Maintenance: Use diagnostic data for predictive maintenance. Monitor trends in current consumption for early fault detection.
Note: This data sheet provides general specifications for the MTL 4541 advanced fieldbus power and communications module. For complete installation guidelines, DIP switch settings, diagnostic interpretation, and safety instructions, consult the official MTL 4500 Series Technical Manual and 4541 Diagnostic Guide. Always verify that the product configuration and certifications match your specific application requirements.
Founded in 2012, ACH is a top-tier distributor of industrial automation products, supplying genuine devices from leading brands like ABB, P+F, E&H, AB, MTL and EMERSON to emerging markets worldwide. Our mission is to provide 100% Genuine products at the most competitive prices, helping customers reduce costs and strengthen their market position.
Long-term brand partners can get competitive product prices. At the same time, ACH controls the profit per order to 5%, providing the most competitive prices.
Yes, all products from ACH are certified genuine OEM units. We acquire our inventory through official OEM channels and trusted third-party suppliers, ensuring every item is authentic and reliable.
We'll handle the shipping for you. Through our partnerships, we can secure competitive rates with major carriers like FedEx, DHL, TNT, and UPS, ensuring a smooth and cost-effective delivery.
One-year Warranty.
Products are divided into spot and futures, and the delivery period of different brands of products is also different. For details, please contact the ACH business manager.
Pessoa de Contato: sales2