Home ProductsMTL Safety Barrier

MTL 5074 Dual-Channel Isolator | 2-Ch, 4-20mA Input, Relay Output, IS, DIN Rail, FM/ATEX

I'm Online Chat Now
Certification
china Achievers Automation Limited certification
china Achievers Automation Limited certification
"ACH has proven to be a reliable partner. Their products are genuine and high-quality, with competitive prices and on-time delivery. We trust them as our long-term supplier in automation."

—— Mohammed Al-Farsi, Procurement

"For us, cost efficiency and authenticity are key. ACH helps reduce expenses while ensuring reliable quality and timely supply, making them a strong partner in our operations."

—— Procurement Manager

"For us, cost efficiency and authenticity are key. ACH helps reduce expenses while ensuring reliable quality and timely supply, making them a strong partner in our operations."

—— Supply Chain Director

"ACH offers quick response, flexible solutions, and fair pricing. The products are always genuine and reliable, and their friendly support makes cooperation smooth."

—— Operations Manager

"ACH provides genuine products with stable quality and fair pricing. Their fast response and reliable delivery give us confidence to continue working with them."

—— Engineering Manager

"We value ACH for their consistent quality and competitive pricing. Deliveries are always reliable, and their professional support makes procurement much easier for our team."

—— Procurement Head

MTL 5074 Dual-Channel Isolator | 2-Ch, 4-20mA Input, Relay Output, IS, DIN Rail, FM/ATEX

MTL 5074 Dual-Channel Isolator | 2-Ch, 4-20mA Input, Relay Output, IS, DIN Rail, FM/ATEX

Large Image :  MTL 5074 Dual-Channel Isolator | 2-Ch, 4-20mA Input, Relay Output, IS, DIN Rail, FM/ATEX Get Best Price

Product Details:
Place of Origin: GB
Brand Name: MTL
Certification: ATEX
Model Number: 5074
Document: ACH-AB-P+F-E+H-IFM-ASCO-YOK...WA.pdf
Payment & Shipping Terms:
Minimum Order Quantity: 1
Price: Negotiable
Packaging Details: carton
Delivery Time: Negotiable
Payment Terms: T/T,XT,ALIPAY
Supply Ability: 100pcs per month
Detailed Product Description
Power Supply: 12-30 V DC (Two-wire) Ambient Temperature: -40°C To 80°C (-40°F To 176°F)
Electrical Rating: General Purpose, Explosion-proof, Intrinsic Safety (depends On Certification) Certifications: Standard Models Include ATEX, IECEx, SIL 2 (consult Manual For Specific Ratings)

MTL 5074 Dual-Channel Isolator | 2-Ch, 4-20mA Input, Relay Output, IS, DIN Rail, FM/ATEX

MTL 5074 dual-channel isolator specifications. 2-channel, 4-20mA input, relay output, intrinsic safety, 24V DC. FM/ATEX/IECEx approved for hazardous areas.


Product Overview

The MTL 5074​ is a dual-channel isolator/converter with relay outputs​ from MTL's 5000 series, designed to interface 4-20mA signals​ from hazardous areas and provide isolated relay outputs. This device provides intrinsic safety protection​ for two input channels, converts analog signals to relay switching functions, and carries FM, ATEX, and IECEx approvals​ for Zone 1 hazardous locations. The "5074" designation identifies this specific model configured for analog input to relay output conversion. This unit provides a versatile solution for alarm, interlock, and control applications where analog signals need to trigger discrete actions.

Technical Specifications

Parameter

Specification

Model Number

5074

Product Series

MTL 5000 Series

Product Type

Dual-Channel Isolator/Converter (Analog Input, Relay Output)

Safety Standard

Intrinsic Safety (IS)

Approvals

FM, ATEX, IECEx (see specific certifications)

Hazardous Area Rating

Zone 1, IIC, T6 (Gas), A21, T85°C (Dust)

Channel Count

2 (independent, galvanically isolated)

Input Specifications


Input Signal

4-20mA DC, 2-wire

Input Impedance

50 Ω

Burnout Detection

Upscale, downscale, or hold (configurable)

Setpoint Adjustment

2 setpoints per channel (adjustable)

Setpoint Accuracy

±0.2% of span

Hysteresis

Adjustable 0.5-10% of span

Output Specifications


Output Type

2 Form A (SPST-NO) relay contacts per channel

Relay Rating

2A @ 30V DC, 0.5A @ 120V AC, 0.3A @ 240V AC

Relay Configuration

Independent relays for each setpoint (4 total relays)

Relay Function

Normally open, close on alarm or on normal (configurable)

Relay Response Time

< 20 ms

General Specifications


Power Supply

20-30V DC (typically 24V DC)

Power Consumption

< 3W (with relays energized)

Isolation

500V AC (input to output, channel to channel, power to I/O)

Operating Temperature

-20°C to +60°C (-4°F to +140°F)

Storage Temperature

-40°C to +85°C (-40°F to +185°F)

Relative Humidity

0-95% non-condensing

Connection Type

Screw terminals

Wire Size

0.2-2.5 mm² (24-12 AWG)

Mounting

DIN rail 35mm

Degree of Protection

IP20 (requires enclosure)

Dimensions (W × H × D)

17.5 × 100 × 115 mm

Weight

Approx. 120 g

Housing Material

Polycarbonate

LED Indicators

2 per channel: Power, Alarm status, Relay status

Configuration

DIP switches and potentiometers

Certifications

FM, ATEX, IECEx, CSA, NEPSI

Note: Specifications are based on MTL 5000 series documentation. The 5074 provides two independent channels with dual setpoints each. Always verify with the latest product datasheet.

Key Features

  • Dual-Channel Design:​ Two independent, galvanically isolated channels

  • Four Relay Outputs:​ Two relays per channel (four total) for flexible alarm/control

  • Adjustable Setpoints:​ Two independently adjustable setpoints per channel

  • Configurable Hysteresis:​ Adjustable 0.5-10% to prevent relay chatter

  • Intrinsic Safety:​ Approved for Zone 1 hazardous locations

  • LED Status Indicators:​ Visual indication of alarm and relay status

  • Easy Configuration:​ Setpoints adjusted via front-panel potentiometers

  • Compact Design:​ Only 17.5mm wide for space-efficient installations

  • Flexible Relay Logic:​ Configurable for normally energized or de-energized operation

  • Global Approvals:​ Certified for international hazardous area applications

Setpoint and Hysteresis Configuration

Parameter

Adjustment Range

Typical Application

Setpoint 1

4-20mA (adjustable)

Low alarm, trip point 1

Setpoint 2

4-20mA (adjustable)

High alarm, trip point 2

Hysteresis

0.5-10% of span

Prevents relay oscillation near setpoint

Relay Logic

Normally energized/de-energized

Fail-safe or non-fail-safe operation

Relay Contact Ratings

Load Type

Maximum Rating

Notes

DC Resistive

2A @ 30V DC


AC Resistive

0.5A @ 120V AC, 0.3A @ 240V AC


DC Inductive

0.5A @ 30V DC (L/R=40ms)

Requires suppression

AC Inductive

0.3A @ 120V AC (cos φ=0.4)

Requires suppression

Lamp Load

0.3A @ 120V AC

Tungsten filament

Entity Parameters (for Hazardous Area Design)

Parameter

Symbol

Value

Unit

Maximum Input Voltage (Ui)

Ui

30

V

Maximum Input Current (Ii)

Ii

30

mA

Maximum External Capacitance (Co)

Co

Dependent on field device

nF

Maximum External Inductance (Lo)

Lo

Dependent on field device

mH

Note: The 5074 is an associated apparatus. Connected 4-20mA transmitters in the hazardous area must be certified as intrinsically safe or be simple apparatus.

Typical Relay Configurations

Application

Setpoint 1

Setpoint 2

Relay Action

High/Low Alarm

Low alarm (e.g., 8mA)

High alarm (e.g., 18mA)

Relay 1: Low alarm, Relay 2: High alarm

Window Alarm

Lower limit

Upper limit

Relay: Active when signal within window

Process Interlock

Trip point

Reset point

Latching or one-shot operation

Pump Control

Start level

Stop level

Automatic pump control

Typical Applications

  • Process Alarm Monitoring:​ High/low alarm generation for pressure, level, temperature

  • Safety Interlocks:​ Trip functions for equipment protection

  • Pump Control:​ Automatic start/stop based on level or pressure

  • Valve Control:​ On/off control based on process conditions

  • Fan Control:​ Start/stop based on temperature or pressure

  • Burner Management:​ Safety interlocks for combustion systems

  • Compressor Control:​ Start/stop and safety shutdown functions

  • Any application requiring​ relay outputs based on 4-20mA process signals in hazardous areas

Important Technical Notes

  1. Field Device Certification:​ 4-20mA transmitters in the hazardous area must be certified as intrinsically safe or qualify as "simple apparatus."

  2. Setpoint Adjustment:​ Setpoints are adjusted via front-panel potentiometers. Use a calibrated current source for accurate setting.

  3. Hysteresis Setting:​ Proper hysteresis prevents relay chatter when the signal is near the setpoint. Typical setting is 1-2% of span.

  4. Relay Load Ratings:​ Do not exceed relay contact ratings. For inductive loads, use appropriate suppression (RC networks, diodes, varistors).

  5. Fail-Safe Design:​ Configure relay logic for appropriate fail-safe operation. Consider what should happen on power loss or sensor failure.

  6. Power Supply:​ Use a certified intrinsically safe power supply or ensure the loop power supply meets IS requirements for the entire circuit.

  7. Grounding:​ Follow manufacturer's grounding recommendations. Proper grounding improves noise immunity and safety.

  8. LED Indicators:​ Green LEDs typically indicate power and normal operation. Red LEDs indicate alarm conditions.

  9. Certification Compliance:​ Verify that the 5074's certifications match the hazardous area classification and temperature rating of your application.

  10. Testing:​ Regularly test alarm functions to ensure proper operation. Document setpoints and test results for maintenance records.


Note: This data sheet provides general specifications for the MTL 5074 dual-channel isolator with relay outputs. For complete installation guidelines, wiring diagrams, configuration procedures, and safety instructions, consult the official MTL 5000 Series Technical Manual. Always verify that the product configuration and certifications match your specific application requirements.

About ACH

Founded in 2012, ACH is a top-tier distributor of industrial automation products, supplying genuine devices from leading brands like ABB, P+F, E&H, AB, MTL and EMERSON to emerging markets worldwide. Our mission is to provide 100% Genuine products at the most competitive prices, helping customers reduce costs and strengthen their market position.

MTL 5074 Dual-Channel Isolator | 2-Ch, 4-20mA Input, Relay Output, IS, DIN Rail, FM/ATEX 1
Frequently Ask & Questions
Are preferential prices available?

Long-term brand partners can get competitive product prices. At the same time, ACH controls the profit per order to 5%, providing the most competitive prices.

Are the Products Genuine OEM Units?

Yes, all products from ACH are certified genuine OEM units. We acquire our inventory through official OEM channels and trusted third-party suppliers, ensuring every item is authentic and reliable.

How will you arrange shipment?

We'll handle the shipping for you. Through our partnerships, we can secure competitive rates with major carriers like FedEx, DHL, TNT, and UPS, ensuring a smooth and cost-effective delivery.

What is the warranty of goods?

One-year Warranty.

How long is the logistics cycle of the product?

Products are divided into spot and futures, and the delivery period of different brands of products is also different. For details, please contact the ACH business manager.

Contact Details
Achievers Automation Limited

Contact Person: sales2

Send your inquiry directly to us