logo
100% genuine products & Actual product photos
Home
Products
Videos
About Us
Factory Tour
Quality Control
Contact Us
Request A Quote
News
Home ProductsWAGO Connectors

WAGO 750-616 PROFIBUS DP Coupler | 32-Channel, 12Mbps, DIN Rail, Modular I/O

I'm Online Chat Now
Certification
china Achievers Automation Limited certification
china Achievers Automation Limited certification
"ACH has proven to be a reliable partner. Their products are genuine and high-quality, with competitive prices and on-time delivery. We trust them as our long-term supplier in automation."

—— Mohammed Al-Farsi, Procurement

"For us, cost efficiency and authenticity are key. ACH helps reduce expenses while ensuring reliable quality and timely supply, making them a strong partner in our operations."

—— Procurement Manager

"For us, cost efficiency and authenticity are key. ACH helps reduce expenses while ensuring reliable quality and timely supply, making them a strong partner in our operations."

—— Supply Chain Director

"ACH offers quick response, flexible solutions, and fair pricing. The products are always genuine and reliable, and their friendly support makes cooperation smooth."

—— Operations Manager

"ACH provides genuine products with stable quality and fair pricing. Their fast response and reliable delivery give us confidence to continue working with them."

—— Engineering Manager

"We value ACH for their consistent quality and competitive pricing. Deliveries are always reliable, and their professional support makes procurement much easier for our team."

—— Procurement Head

WAGO 750-616 PROFIBUS DP Coupler | 32-Channel, 12Mbps, DIN Rail, Modular I/O

WAGO 750-616 PROFIBUS DP Coupler | 32-Channel, 12Mbps, DIN Rail, Modular I/O

Large Image :  WAGO 750-616 PROFIBUS DP Coupler | 32-Channel, 12Mbps, DIN Rail, Modular I/O Get Best Price

Product Details:
Place of Origin: DE
Brand Name: WAGO
Certification: ATEX
Model Number: 750-616
Document: ACH-AB-P+F-E+H-IFM-ASCO-YOK...WA.pdf
Payment & Shipping Terms:
Minimum Order Quantity: 1
Price: Negotiable
Packaging Details: carton
Delivery Time: Negotiable
Payment Terms: T/T,XT,ALIPAY
Supply Ability: 100pcs per month
Detailed Product Description
Power Supply: 12-30 V DC (Two-wire) Ambient Temperature: -40°C To 80°C (-40°F To 176°F)
Electrical Rating: General Purpose, Explosion-proof, Intrinsic Safety (depends On Certification) Certifications: Standard Models Include ATEX, IECEx, SIL 2 (consult Manual For Specific Ratings)
Highlight:

WAGO 750-616 PROFIBUS DP Coupler

,

32-channel modular I/O coupler

,

DIN rail PROFIBUS DP connector

WAGO 750-616 PROFIBUS DP Coupler | 32-Channel, 12Mbps, DIN Rail, Modular I/O

WAGO 750-616 PROFIBUS DP fieldbus coupler specifications. 12Mbps, 32-channel capacity, modular I/O, 24V DC. Connects WAGO-I/O-SYSTEM to PROFIBUS DP networks.


Product Overview

The WAGO 750-616​ is a fieldbus coupler​ for the WAGO-I/O-SYSTEM, designed to connect WAGO's modular electronic terminal blocks (I/O modules)​ to a PROFIBUS DP network. It acts as the intelligent network interface and controller​ for a local I/O station. Supporting PROFIBUS DP-V1​ with data rates up to 12 Mbps, it can manage a 32-channel (module) local bus​ and provides the power and communication interface​ for connected digital, analog, and special function modules. It is a core component for building distributed I/O nodes on a PROFIBUS DP network.

Technical Specifications

Parameter

Specification

Article Number

750-616

Product Type

Fieldbus Coupler for PROFIBUS DP

Series

WAGO-I/O-SYSTEM 750

Fieldbus Protocol

PROFIBUS DP (DP-V1)

Data Transfer Rate

9.6 kbps to 12 Mbps (auto-detect)

Address Setting

Rotary switch (0-99) + 1 DIP switch (x100) for addresses 0-125

Maximum Local Bus Modules

32 modules (64 bytes of process data, configurable)

Internal Backplane Power

5V, 2A maximum for connected modules

Internal Bus Voltage

24V DC (from power feed module) for sensors/actuators

External Supply (Terminal X4)

24V DC (20.4V - 28.8V) for coupler electronics

Current Consumption

Typically 60mA @ 24V DC (electronics)

Power Feed Module

Required (e.g., 750-600/040-000) for 24V field power

Communication Interface

9-pin D-Sub, RS-485, with termination resistor switch

Status Indicators

4 LEDs: Power (PWR), BUSF (Bus Fault), RUN, ERR

Data Width (Process Image)

Configurable, up to 244 bytes input + 244 bytes output

Diagnostic Functions

Yes, configurable via WAGO-I/O-CHECK or PLC

GSD/GSDML File

Yes, required for PLC configuration

Configuration Software

WAGO-I/O-CHECK, WAGO-I/O-PRO, or PLC configuration tool

Clock Synchronization

No

Operating Temperature

0°C to +55°C

Storage Temperature

-25°C to +85°C

Relative Humidity

95%, non-condensing

Degree of Protection

IP20

Mounting

35mm DIN Rail (EN 60715)

Connection Technology

CAGE CLAMP® S for 2.5mm² (14 AWG) conductors

Width

24mm (2 ETS points)

Certifications

CE, UL, CSA, ATEX, DNV GL, GL, others

Note: Specifications are based on the WAGO-I/O-SYSTEM 750 datasheet. Always verify with the latest documentation.

Key Features

  • PROFIBUS DP-V1 Interface:​ Connects modular I/O to a PROFIBUS DP master (e.g., Siemens PLC)

  • High Channel Density:​ Controls up to 32 I/O modules (digital, analog, special) on the local bus

  • 12 Mbps Communication:​ Supports the maximum PROFIBUS DP data rate

  • Modular and Flexible:​ I/O configuration can be customized for any application

  • Easy Addressing:​ Rotary and DIP switches for setting the PROFIBUS DP station address (0-125)

  • Integrated Diagnostics:​ LEDs and diagnostic data for quick troubleshooting

  • Auto Baud Detection:​ Automatically detects the network baud rate

  • Standard GSD File:​ Easy integration into Siemens STEP 7, TIA Portal, or other PLC engineering tools

  • Powerful Local Bus:​ Supplies 5V/2A for module electronics and manages 24V field power distribution

  • WAGO CAGE CLAMP®:​ Tool-free, maintenance-free connection technology

Physical Layout and Terminals

Terminal

Label

Function

Description

X1

A1, B1

PROFIBUS DP In

Network connection from the previous node/master.

X2

A2, B2

PROFIBUS DP Out

Network connection to the next node.

X3

FG

Functional Ground

Ground connection for shielding.

X4

24V, 0V

Electronics Power

24V DC supply for the coupler's internal electronics.

LEDs

PWR, BUSF, RUN, ERR

Status Indicators

Visual status of power, bus, operation, and errors.

Status LED Indicators

LED

Color

State

Meaning

PWR

Green

On

24V DC electronics supply is present and OK.

BUSF

Red

On

Bus fault (e.g., wiring error, baud rate mismatch, no master).

BUSF

Red

Flashing

The coupler is not configured in the master's configuration.

RUN

Green

On

The coupler is operating correctly, data exchange is active.

ERR

Red

On

Local bus error (e.g., module failure, configuration mismatch, watchdog).

Addressing via Rotary and DIP Switches

Address Range

DIP Switch 1 (x100)

Rotary Switch (0-99)

Example Setting for Address 45

0 - 99

OFF

0-99

DIP: OFF, Rotary: 45

100 - 125

ON

0-25

DIP: ON, Rotary: 25 (for address 125)

The DIP switch is located next to the rotary switch. DIP Switch ON adds 100 to the rotary switch value.

Typical System Configuration

[PROFIBUS DP Master/PLC]
        |
[PROFIBUS DP Cable] --- 750-616 Coupler (Address, e.g., 3) --- [PROFIBUS DP Cable to next node...]
                                |
                    [WAGO 750-600 Power Feed Module]
                                |
        [WAGO 750-5xx Digital/Analog I/O Modules] (up to 32)

Installation Steps

  1. Mounting:​ Mount the coupler on a 35mm DIN rail.

  2. Addressing:​ Set the unique PROFIBUS DP address (0-125) using the rotary and DIP switches.

  3. Wiring:​ Connect the 24V DC supply to terminals X4 (24V, 0V). Connect the PROFIBUS DP network cable to terminals X1 (In) and X2 (Out). Connect the functional ground (X3).

  4. Power Feed Module:​ Insert the required 24V power feed module (e.g., 750-600) directly to the right of the coupler.

  5. I/O Modules:​ Insert and configure the required digital, analog, and special function modules.

  6. Configuration:​ Use the GSD file in the PLC configuration tool (e.g., Siemens STEP 7) to configure the station's I/O layout.

  7. Commissioning:​ Apply power, verify LED status, and start data exchange with the master.

Software and Configuration

  • GSD File:WAGO0B06.GSD(specific file version required, available from WAGO website).

  • Configuration Tools:​ Configure within the PLC engineering software (e.g., Siemens TIA Portal, STEP 7) or using WAGO-I/O-CHECK for stand-alone configuration.

  • Process Image:​ Define the input and output data areas in the PLC configuration.

Typical Applications

  • Distributed I/O Stations:​ Replacing hardwired signals with a PROFIBUS DP network

  • Machine Control:​ Modular I/O for packaging, assembly, and material handling machines

  • Process Skids:​ Pre-fabricated control systems for process industries

  • Building Automation:​ HVAC, lighting, and access control

  • Retrofit Projects:​ Upgrading existing panels to networked I/O

  • Any application​ requiring a flexible, modular remote I/O station on PROFIBUS DP

Important Technical Notes

  1. Power Supply:​ The 24V DC supply on X4 powers the coupler's electronics only. A separate 750-600 series power feed module is mandatory​ to provide 24V power to the connected I/O modules and field devices.

  2. Address Conflicts:​ Ensure each 750-616 on the network has a unique address between 0 and 125.

  3. Bus Termination:​ The first and last node on the PROFIBUS DP segment must have termination enabled. The 750-616 has a termination resistor switch for this purpose.

  4. Module Limit:​ The 32-module limit refers to physical modules, not channels. Complex modules (e.g., 8-channel analog input) count as one module.

  5. Configuration:​ The I/O layout configured in the PLC must match the physical module order on the local bus.

  6. GSD File:​ Always use the latest GSD file from the WAGO website for full functionality and compatibility.

  7. Grounding:​ Always connect the functional ground (FG, terminal X3) to the cabinet ground for optimal noise immunity.


Note: This data sheet provides general specifications for the WAGO 750-616 PROFIBUS DP coupler. For complete installation guidelines, wiring diagrams, GSD file, configuration procedures, and safety instructions, consult the official WAGO-I/O-SYSTEM 750 Manual​ and the product-specific data sheet. Always verify module compatibility and power budget calculations for your specific I/O configuration.

About ACH

Founded in 2012, ACH is a top-tier distributor of industrial automation products, supplying genuine devices from leading brands like ABB, P+F, E&H, AB, MTL and EMERSON to emerging markets worldwide. Our mission is to provide 100% Genuine products at the most competitive prices, helping customers reduce costs and strengthen their market position.

WAGO 750-616 PROFIBUS DP Coupler | 32-Channel, 12Mbps, DIN Rail, Modular I/O 1
Frequently Ask & Questions
Are preferential prices available?

Long-term brand partners can get competitive product prices. At the same time, ACH controls the profit per order to 5%, providing the most competitive prices.

Are the Products Genuine OEM Units?

Yes, all products from ACH are certified genuine OEM units. We acquire our inventory through official OEM channels and trusted third-party suppliers, ensuring every item is authentic and reliable.

How will you arrange shipment?

We'll handle the shipping for you. Through our partnerships, we can secure competitive rates with major carriers like FedEx, DHL, TNT, and UPS, ensuring a smooth and cost-effective delivery.

What is the warranty of goods?

One-year Warranty.

How long is the logistics cycle of the product?

Products are divided into spot and futures, and the delivery period of different brands of products is also different. For details, please contact the ACH business manager.

Contact Details
Achievers Automation Limited

Contact Person: sales2

Send your inquiry directly to us